Hanging Heptafluoropropane Fire Extinguishing System
The suspended heptafluoropropane gas fire suppression system (temperature-sensitive type) consists of a fire extinguishing agent cylinder, a temperature-sensitive release assembly, a suspension bracket, a pressure gauge, and other components. It does not require installation of fire extinguishing agent delivery pipelines, does not need a dedicated cylinder room, and does not need to be linked with a fire alarm system. It can be installed either by suspension or wall mounting. When a fire occurs, the temperature-sensitive glass bulb breaks, triggering the temperature-sensitive release assembly to open and directly spray the fire extinguishing agent into the protected area. As a result, there is no pipeline loss of the extinguishing agent, leading to faster extinguishing speeds and higher efficiency.
Category:
Detailed description
Overview
The suspended heptafluoropropane gas fire suppression system (temperature-sensitive type) consists of a fire extinguishing agent cylinder, a temperature-sensitive release assembly, a suspension bracket, a pressure gauge, and other components. It does not require installation of fire extinguishing agent delivery pipelines, does not need a dedicated cylinder room, and does not need to be linked with a fire alarm system. It can be installed either by suspension or wall mounting. When a fire occurs, the temperature-sensitive glass bulb breaks, triggering the temperature-sensitive release assembly to open and directly spray the fire extinguishing agent into the protected area. As a result, there is no pipeline loss of the extinguishing agent, leading to faster extinguishing speeds and higher efficiency.
Fire extinguishing principle
When a fire occurs within the protected area, the temperature-sensitive glass bulb on the suspended heptafluoropropane gas fire suppression system (temperature-sensing type) expands upon heating, causing it to rupture and open the valve, thereby releasing the extinguishing agent to put out the fire.
Technical Parameters
| Product Model Specifications | XQQW10/1.6-HZ | XQQW20/1.6-HZ | XQQW30/1.6-HZ |
|---|---|---|---|
| Fire extinguishing agent cylinder capacity (L) | 10 | 20 | 30 |
| Device diameter (mm) | 300 | 350 | 350 |
| Device height (mm) | 256 | 334 | 438 |
| Fire extinguishing agent storage pressure | 1.6 MPa (20℃) | ||
| Maximum working pressure | 2.5 MPa (20℃) | ||
| Fire extinguishing agent filling density | ≤1150 kg/m³ | ≤1000 kg/m³ | |
| Fixed-temperature heat-sensitive glass bulb | Activation temperature: 68℃ | ||
| Fire suppression techniques | Full submersion | ||
| Fire extinguishing agent discharge time | ≤10 S | ||
| Startup method | Thermal glass bulb with fixed temperature activation | ||
| Drive gas | Nitrogen | ||
| Operating ambient temperature | 0℃ to 50℃ | ||
Note: The model designation for suspended heptafluoropropane fire suppression systems is as follows: For example, XQQW10/1.6-HZ. In this designation: XQ stands for suspended gas fire suppression system; Q stands for heptafluoropropane; W indicates that the activation method is a fixed-temperature thermal bulb actuator; 10 represents a fire extinguishing agent storage bottle capacity of 10 liters; 1.6 denotes a storage pressure of 1.6 MPa; and HZ is the Hezhi brand mark. |
|||