  • undefined

Hanging Heptafluoropropane Fire Extinguishing System

The suspended heptafluoropropane gas fire suppression system (temperature-sensitive type) consists of a fire extinguishing agent cylinder, a temperature-sensitive release assembly, a suspension bracket, a pressure gauge, and other components. It does not require installation of fire extinguishing agent delivery pipelines, does not need a dedicated cylinder room, and does not need to be linked with a fire alarm system. It can be installed either by suspension or wall mounting. When a fire occurs, the temperature-sensitive glass bulb breaks, triggering the temperature-sensitive release assembly to open and directly spray the fire extinguishing agent into the protected area. As a result, there is no pipeline loss of the extinguishing agent, leading to faster extinguishing speeds and higher efficiency.

Telephone:

(Mr.Hu)

Detailed description

   Overview

  The suspended heptafluoropropane gas fire suppression system (temperature-sensitive type) consists of a fire extinguishing agent cylinder, a temperature-sensitive release assembly, a suspension bracket, a pressure gauge, and other components. It does not require installation of fire extinguishing agent delivery pipelines, does not need a dedicated cylinder room, and does not need to be linked with a fire alarm system. It can be installed either by suspension or wall mounting. When a fire occurs, the temperature-sensitive glass bulb breaks, triggering the temperature-sensitive release assembly to open and directly spray the fire extinguishing agent into the protected area. As a result, there is no pipeline loss of the extinguishing agent, leading to faster extinguishing speeds and higher efficiency.

   Fire extinguishing principle

  When a fire occurs within the protected area, the temperature-sensitive glass bulb on the suspended heptafluoropropane gas fire suppression system (temperature-sensing type) expands upon heating, causing it to rupture and open the valve, thereby releasing the extinguishing agent to put out the fire.

   Technical Parameters

Product Model Specifications XQQW10/1.6-HZ XQQW20/1.6-HZ XQQW30/1.6-HZ
Fire extinguishing agent cylinder capacity (L) 10 20 30
Device diameter (mm) 300 350 350
Device height (mm) 256 334 438
Fire extinguishing agent storage pressure 1.6 MPa (20℃)
Maximum working pressure 2.5 MPa (20℃)
Fire extinguishing agent filling density ≤1150 kg/m³ ≤1000 kg/m³
Fixed-temperature heat-sensitive glass bulb Activation temperature: 68℃
Fire suppression techniques Full submersion
Fire extinguishing agent discharge time ≤10 S
Startup method Thermal glass bulb with fixed temperature activation
Drive gas Nitrogen
Operating ambient temperature 0℃ to 50℃

Note: The model designation for suspended heptafluoropropane fire suppression systems is as follows: For example, XQQW10/1.6-HZ. In this designation: XQ stands for suspended gas fire suppression system; Q stands for heptafluoropropane; W indicates that the activation method is a fixed-temperature thermal bulb actuator; 10 represents a fire extinguishing agent storage bottle capacity of 10 liters; 1.6 denotes a storage pressure of 1.6 MPa; and HZ is the Hezhi brand mark.

Consultation price

Action
Submit a request for quotation