Single-cabinet heptafluoropropane
A cabinet-type heptane gas fire suppression system, also known as a pre-engineered fire suppression system, is a type of fire suppression system in which the fire extinguishing agent storage unit, piping, nozzles, signal feedback devices, and actuation components are pre-assembled into a complete unit.
Category:
Detailed description
Overview
The cabinet-type heptafluoropropane gas fire suppression system, also known as a pre-engineered fire suppression system, is a type of fire suppression equipment that comes pre-assembled with all necessary components—such as the extinguishing agent storage unit, piping, nozzles, signal feedback devices, and actuation mechanisms—in a single package. The cabinet-type automatic fire suppression systems manufactured by our company are suitable for unit-independent total flooding fire suppression systems, where one or several cabinet-type fire suppression units protect a single protected zone. The volume of the storage unit, the amount of extinguishing agent charged, and the activation method can all be specifically designed according to the requirements of the particular project. Typically, this system is linked to an automatic fire detection and suppression control system, enabling it to provide comprehensive protection for the protected zone and automatically detect fires, issue alarms, and initiate fire suppression upon detection of a fire event.
Fire extinguishing principle
After the cabinet-type heptafluoropropane gas fire suppression system is installed, the fire suppression system enters automatic operation mode. When a fire occurs within the protected area, fire detectors such as heat and smoke detectors transmit fire alarm signals to the gas fire suppression controller. The controller then outputs signals to activate the interlinked equipment and issues an audible and visual alarm. After a delay of 0 to 30 seconds (which can be adjusted according to actual needs), the controller sends a start signal, thereby opening the container valve of the extinguishing agent cylinder assembly. The heptafluoropropane extinguishing agent is then released into the protected area through connecting pipes and nozzles to carry out fire suppression.
Scope of application
● Suitable for extinguishing the following types of fires: electrical fires, liquid fires, fires involving fusible solids, and surface fires on solids. For gas fires, the gas supply must be shut off before firefighting can begin.
● Suitable for protecting enclosed spaces, typical applications include: fire protection zones containing flammable gases and liquids with explosion hazards; libraries, archives, document and cultural relic storage facilities; oil-immersed transformers, switchgear rooms equipped with oil-filled switches, and emergency generator rooms; as well as telecommunications equipment rooms and electronic computer rooms.
Basic Parameters
| Model |
Cabinet-style |
Startup delay |
0~30S |
|---|---|---|---|
| Working pressure (20℃) |
2.5MPa |
Starting current |
DC24V/1.6A |
| Maximum working pressure |
4.2MPa |
Jetting time |
≤10S |
| Ambient temperature |
0℃~50℃ |
Fire extinguishing method |
Full submersion |
| Startup method |
Electric and mechanically manual start |
Implementation standard |
GB 16670-2006 |
| Model |
Storage bottle specifications |
Fire extinguishing agent filling density kg/m³ |
Cylinder outer diameter dimensions Φ × H height (mm) |
Cabinet external dimensions (mm) |
|---|---|---|---|---|
| GQQ40/2.5-HZ |
40L |
≤1150 |
300×757 |
1200×450×500 |
| GQQ70/2.5-HZ |
70L |
≤1150 |
350×912 |
1400×450×500 |
| GQQ90/2.5-HZ |
90L |
≤1150 |
350×1120 |
1700×450×500 |
| GQQ100/2.5-HZ |
100L |
≤1150 |
350×1225 |
1700×450×500 |
| GQQ120/2.5-HZ |
120L |
≤1000 |
350×1425 |
1900×450×500 |
| GQQ150/2.5-HZ |
150L |
≤1000 |
400×1387 |
1900×500×520 |
| GQQ180/2.5-HZ |
180L |
≤1000 |
400×1627 |
2100×500×520 |
| GQQ70×2/2.5-HZ |
70L |
≤1150 |
350×912 |
1400×450×980 |
| GQQ90×2/2.5-HZ |
90L |
≤1150 |
350×1120 |
1700×450×980 |
| GQQ100×2/2.5-HZ |
100L |
≤1150 |
350×1225 |
1700×450×980 |
| GQQ120×2/2.5-HZ |
120L |
≤1000 |
350×1425 |
1900×450×980 |
| GQQ150×2/2.5-HZ |
150L |
≤1000 |
400×1387 |
1900×500×980 |
| Note: |
Model designation for cabinet-type heptafluoropropane fire suppression systems: For example, GQQ90/2.5HZ. G – Cabinet-type fire suppression system; Q – Gas-based fire suppression; Q – Heptafluoropropane; GQQ stands for cabinet-type heptafluoropropane fire suppression system; 90 – The volume of the extinguishing agent cylinder is 90 liters; 2.5 – The storage pressure is 2.5 MPa; HZ – Represents the Hezhi brand mark. | |||