Non-pressurized ultra-fine dry powder fire extinguishing system
The device employs a novel drive agent (solid-to-gas conversion), which outperforms other similar products that use gas-driven agents. It features low noise, minimal recoil, and long duration of operation. When multiple units are linked together, they will not cause secondary damage to protected objects or buildings. With its small nozzle and splash-disk design, this device fully leverages the highly effective fire-extinguishing performance of ultra-fine dry powder extinguishing agents, making it an ideal next-generation automatic fire suppression product.
Category:
Detailed description
Overview
The device employs a novel drive agent (solid-to-gas conversion), which outperforms other similar products that use gas-driven agents. It features low noise, minimal recoil, and long duration of action. When multiple units are linked together, they will not cause secondary damage to protected objects or buildings. With its small nozzle and splash-disk design, this device fully leverages the highly effective fire-extinguishing performance of ultra-fine dry powder extinguishing agents, making it an ideal next-generation automatic fire suppression product.
Working principle
When the activation signal (either automatic or manual) is triggered, the initiator ignites the gas-generating agent. The gas-generating agent is activated and rapidly produces gas. As the gas expands quickly within the enclosure, the internal pressure inside the enclosure increases. Once the gas pressure reaches a certain threshold, the gas thoroughly mixes with the ultra-fine dry powder, causing the aluminum membrane at the nozzle to rupture. The ultra-fine dry powder extinguishing agent is then rapidly ejected into the protected area and swiftly spreads outward in all directions, forming a fully submerged mist-like extinguishing state. Under the combined physical and chemical effects of the ultra-fine dry powder extinguishing agent, the flames are effectively extinguished.
| Model |
Fire extinguishing agent weight (kg) |
Injection time (s) |
Protection space (m³) |
Product dimensions (mm) |
Operating temperature range (℃) |
|---|---|---|---|---|---|
| FZX-ACT2-HZ |
2 |
≤5S |
17 |
Φ220×426 |
-40℃~50℃ |
| FZX-ACT3-HZ |
3 |
20 |
Φ220×426 |
||
| FZX-ACT4-HZ |
4 |
33 |
Φ270×455 |
||
| FZX-ACT5-HZ |
5 |
33 |
Φ270×455 |
||
| FZX-ACT6-HZ |
6 |
50 |
Φ285×442 |
||
| FZX-ACT7-HZ |
7 |
47 |
Φ285×506 |
||
| FZX-ACT-HZ |
8 |
≤10S |
53 |
Φ285×506 |
|
| FZX-ACT10-HZ |
10 |
67 |
Φ350×507 |
Note Model designation for pressurized ultra-fine dry powder fire extinguishing systems: For example, FFX-ACT2-HZ. F – Dry powder fire extinguishing system; F – Pressurized type; X – Suspended installation; A – ABC dry powder; C – Ultra-fine dry powder; T – Standard application environment; 2 – Dry powder weight: 2 kg; HZ – Hezhi brand mark.